Tripp Lite SUINT3000RTXL2U uninterruptible power supply (UPS) Double-conversion (Online) 3 kVA 2500 W 10 AC outlet(s)

Tripp Lite SUINT3000RTXL2U uninterruptible power supply (UPS) Double-conversion (Online) 3 kVA 2500 W 10 AC outlet(s)

SmartOnline Double-Conversion UPS - 2U, USB, DB9, 230V, 3kVA, 2.5kW, On-Line

Trade Prices

Distributor Product SKU Stock Updated Price
Anixter 2U SMARTONLINE 3KVA DOUBLECONVERSION UPS C13/C19 OUTLETS200-240V 543083 Register free see stock
ASI Corp UPS SUINT3000RTXL2U SmartOnline Double-Conversion UPS 2U USB DB9 229438
BlueStar TRIPP LITE, SMARTONLINE 208/240, 230V 3KVA 2.5KW DOUBLE-CONVERSION UPS, 2U RACK/TOWER, EXTENDED RUN, SNMPWEBCARD OPTION, USB, DB9 SERIAL SUINT3000RTXL2U

Related Products

Description

Double-Conversion UPS Protects Equipment against Damage, Downtime and Data Loss
This 230V 2U UPS system protects connected equipment against damage, downtime and data loss due to power outages, voltage fluctuations and transient surges. Featuring a 2500W capacity, high 0.8 power factor, 420 joules of surge suppression, true on-line operation with pure sine wave output and zero transfer time to battery, the SmartOnline® SUINT3000RTXL2U double-conversion UPS provides the highest level of battery backup and AC power protection for critical network closet, computer room and data center equipment.

Individually Controllable Load Banks Let You Access and Control Outlets
Eight C13 outlets are even split into two switchable load banks, each allowing you to reboot connected equipment or shed loads remotely. In addition to the C13 outlets, this UPS provides two C19 outlets for powering critical components.

Reliable, Expandable Battery Backup Keeps You Operational Through Power Outages
UPS battery backup keeps connected equipment operational through short power failures, and provides time to save data and perform an orderly system shutdown in case of a prolonged blackout. The field-replaceable, hot-swappable internal battery provides 15 minutes of support at half load and six minutes at full load. During normal operation, incoming utility power keeps the battery fully charged so backup power will be available when needed. For mission-critical applications demanding continuous uptime, the 3kVA UPS can provide expandable runtime with optional external battery packs, such as Tripp Lite’s BP72V15-2U (sold separately).

Easily Hot-Swappable with No Expensive Service Calls or Downtime Needed
Tripp Lite’s optional PDUBHV20 bypass PDU (sold separately) enables hot-swappable UPS replacement with no disruption of power to connected equipment. When making repairs or replacing a battery, no lengthy service calls or downtime are necessary.

Optional WEBCARDLX Network Interface Offers 24/7 Remote Access for Monitoring and Control
The optional WEBCARDLX (sold separately) with the latest version of PowerAlert Device Manager firmware (PADM20) provides enhanced remote management capabilities, including customizable dashboard graphs to fit user preferences. The PADM20 upgrade and Tripp Lite’s PowerAlert Element Manager (PAEM) software form a powerful tool for expanding maintenance functions in large installations, including firmware update checks and backup and restoration of device configurations. Auto Probe allows a UPS with switched loads to automatically reboot devices if a network communication failure is detected. This preserves uptime and minimizes the time and expense associated with on-site support.

Intuitive Front-Panel Interface for Convenient UPS Operation and Monitoring
Front-panel LEDs provide information on load and battery levels, operating mode, fault status and other critical data at a glance. The LED panel rotates for comfortable viewing in rack-mount or tower configuration.

Advanced Communications Ports
This USB UPS system has USB and DB9 ports (cables are included) that enable data-saving unattended shutdown of connected systems when used with Tripp Lite’s free downloadable PowerAlert® software. Capabilities include detailed monitoring of load levels, self-test data and utility power conditions.

Versatile Installation Options
Hardware is included for mounting the UPS system in 2U of space in an EIA-standard 19-inch 4-post rack with a depth of only 66 centimeters (26 inches). Use the optional 2POSTRMKITWM (sold separately) for 2-post rack mounting or the optional 2-9USTAND (sold separately) for mounting in an upright tower position. The C20 power inlet accepts a variety of user-supplied input cords.

Specifications

Power
Output power2500 W
Input operation voltage (min)200 V
Input operation voltage (max)240 V
Output operation voltage (min)200 V
Output operation voltage (max)240 V
Surge energy rating420 J
Maximum current15 A
Efficiency97%
Emergency Power Off (EPO)Yes
Power factor0.8
Crest factor3:1
Output power capacity3 kVA
Input frequency50/60 Hz
Ports & interfaces
Cable length120.1" (3.05 m)
AC outlets quantity10 AC outlet(s)
AC outlet typesC13 coupler, C19 coupler
Power plugC20 coupler
USB 2.0 ports quantity1
Serial ports quantity1
Performance
UPS topologyDouble-conversion (Online)
Response time0 ms
LED indicatorsYes
Power protection featuresOver voltage, Under voltage
Audible alarm(s)Yes
Features
Country of originChina
UPS topologyDouble-conversion (Online)
Response time0 ms
Output power2500 W
Input operation voltage (min)200 V
Input operation voltage (max)240 V
Output operation voltage (min)200 V
Output operation voltage (max)240 V
Surge energy rating420 J
Maximum current15 A
Efficiency97%
Emergency Power Off (EPO)Yes
Power protection featuresOver voltage, Under voltage
Power factor0.8
Crest factor3:1
Audible alarm(s)Yes
Output power capacity3 kVA
Input frequency50/60 Hz
Battery
Typical backup time at half load15 min
Typical backup time at full load6 min
Hot-swap batteryYes
Cold startYes
Design
Country of originChina
Rack capacity2U
Form factorRackmount
LED indicatorsYes
Product colourBlack
Cooling typeActive
CertificationUL1778, CSA, CE, FCC-15 A, TAA
Cable length120.1" (3.05 m)
Housing materialSteel
Operational conditions
Operating temperature (T-T)0 - 40 °C
Storage temperature (T-T)-15 - 50 °C
Operating relative humidity (H-H)0 - 95%
Cooling
Cooling typeActive
Weight & dimensions
Package width23.7" (602 mm)
Package depth29.8" (756.9 mm)
Package height9.7" (246.4 mm)
Weight68.8 lbs (31.2 kg)
Width17.2" (437.9 mm)
Package weight84.7 lbs (38.4 kg)
Height3.46" (87.9 mm)
Depth24.3" (616 mm)
Packaging data
Package width23.7" (602 mm)
Package depth29.8" (756.9 mm)
Package height9.7" (246.4 mm)
Package weight84.7 lbs (38.4 kg)
Logistics data
Products per master (outer) case1 pc(s)
Master (outer) case width23.7" (602 mm)
Master (outer) case length29.8" (756.9 mm)
Master (outer) case height9.7" (246.4 mm)
Master (outer) case gross weight84.7 lbs (38.4 kg)
Certificates
CertificationUL1778, CSA, CE, FCC-15 A, TAA