Tripp Lite SUINT2000LCD1U uninterruptible power supply (UPS) Double-conversion (Online) 2 kVA 1600 W 5 AC outlet(s)

Tripp Lite SUINT2000LCD1U uninterruptible power supply (UPS) Double-conversion (Online) 2 kVA 1600 W 5 AC outlet(s)

SmartOnline 2000VA 1600W 208/230V Double-Conversion UPS - 5 Outlets, Network Card Option, LCD, USB, DB9, 1U Rack

Trade Prices

Distributor Product SKU Stock Updated Price
D&H UPS 230V 2000VA 1.6KW 1U LCD SUINT2000LCD1U Register free see stock
Ingram Micro UPS SMART ONLINE 2200VA HJ9777
TD Synnex 230V 2000VA 1.6KW DOUBLE-CONVERSION UPS 8809016

Related Products

Description

Double-Conversion UPS Protects Equipment Against Damage, Downtime and Data Loss
This 1U on-line double-conversion UPS system with battery-independent restart maintains perfect output by converting AC input to DC, then reconverting UPS output to fully regulated sine wave AC. Constant on-line operation completely isolates sensitive equipment from every power problem on the AC line. The SmartOnline® SUINT2000LCD1U provides the highest level of power protection and battery backup for servers, switches, phone systems, kiosks and professional A/V computer systems in IT applications where rack space is limited and a 1U UPS is desired.

Reliable, Expandable Battery Backup Keeps You Operational Through Power Outages
The field-replaceable, hot-swappable VRLA internal battery allows you to work through short power failures and give you enough time to safely save files and shut down your system in case of a prolonged blackout. Zero transfer time between on-line and battery modes maintains continuous operation of connected equipment without interruption or rebooting.

Optional LX Platform Network Management Card Allows Remote Access 24/7
The WEBCARDLXE network interface (sold separately) enables full remote configuration and management, including load shedding, reboots of connected equipment and safe shutdowns. The IP-based Auto Probe feature ensures continuous network uptime by communicating with other network devices, detecting lost connectivity and automatically rebooting IT equipment. Optional EnviroSense2 modules (E2MT, E2MTDO and E2MTHDI, all sold separately) provide a variety of environmental monitoring and control options.

C13 Outlets Protect Your Connected Components
Five C13 outlets provide connected equipment with pure sine wave AC output and allow you to monitor power consumption down to the outlet group level. Power provided by these outlets is filtered to protect connected equipment against damaging surges and line noise. The outlets are grouped into two individually controllable load banks that let you shed non-critical loads to extend runtime for critical loads.

Premium Protection from EMI/RFI Line Noise Helps Your Equipment Perform Better
This UPS system filters out disruptive electromagnetic and radio frequency interference that can inflict hardware damage or data loss. This EMI/RFI filtering also helps your connected components perform better and last longer.

Clear LCD Interface Keeps You Informed at a Glance
The menu-driven front-panel LCD provides detailed settings, alarms and notifications to help diagnose any issues. It provides voltage, frequency, battery, load and other critical information. Audible alarms can be disabled through the front menu when the UPS goes to battery power. LEDs indicate AC output status and shutdown/fault condition.

Advanced Communications Ports Allow for Automatic Saves and Shutdowns
RS-232 and USB ports connect to a device for a variety of communication options (cables are included). A dry-contact relay port can be programmed through the LCD to provide reliable communications to automation and industrial components. The EPO/ROO port permits emergency shutdown or remote restart of all connected equipment.

Needs Only 1U of Rack Space for Installation
You can mount the SUINT2000LCD1U in just 1U of space in an EIA-standard 19-inch 4-post rack using the included hardware. The six-foot (1.8-meter) power cord with C14 plug connects to a compatible AC outlet. An internal fan helps keep the UPS cool in a crowded enclosure.

Specifications

Power
Output voltage regulation3%
Output power1600 W
Input operation voltage (min)200 V
Input operation voltage (max)240 V
Output operation voltage (min)200 V
Output operation voltage (max)240 V
Surge energy rating540 J
Maximum current20 A
Power factor0.8
Input current Total Harmonic Distortion (THD)8%
Crest factor3:1
Output power capacity2 kVA
Efficiency (On-line mode)90%
Efficiency (ECO mode)98%
Input frequency50/60 Hz
Ports & interfaces
Cable length70.9" (1.8 m)
AC outlets quantity5 AC outlet(s)
AC outlet typesC13 coupler
Power plugC14 coupler
Performance
Audible alarm modesFault, Low battery alarm, Overload alarm
UPS topologyDouble-conversion (Online)
WaveformPure sine
Number of input phases1
LED indicatorsYes
EMI/RFI noise filteringYes
Noise level65 dB
Audible alarm(s)Yes
Features
Audible alarm modesFault, Low battery alarm, Overload alarm
UPS topologyDouble-conversion (Online)
WaveformPure sine
Output voltage regulation3%
Number of input phases1
Output power1600 W
Input operation voltage (min)200 V
Input operation voltage (max)240 V
Output operation voltage (min)200 V
Output operation voltage (max)240 V
Surge energy rating540 J
Maximum current20 A
EMI/RFI noise filteringYes
Power factor0.8
Noise level65 dB
Input current Total Harmonic Distortion (THD)8%
Crest factor3:1
Audible alarm(s)Yes
Output power capacity2 kVA
Efficiency (On-line mode)90%
Efficiency (ECO mode)98%
Input frequency50/60 Hz
Battery
Battery voltage48 V
Battery technologySealed Lead Acid (VRLA)
Typical backup time at half load10 min
Typical backup time at full load3 min
Hot-swap batteryYes
Cold startYes
Design
Rack capacity1U
Form factorRackmount
LED indicatorsYes
Product colourBlack
Cooling typeActive
Cable length70.9" (1.8 m)
Built-in fanYes
Housing materialSteel
Display typeLCD
Operational conditions
Operating temperature (T-T)0 - 40 °C
Storage temperature (T-T)-15 - 50 °C
Operating relative humidity (H-H)0 - 95%
Storage relative humidity (H-H)0 - 95%
Operating altitude0 - 39370.1" (0 - 1000 m)
Technical details
Sustainability complianceYes
Sustainability certificatesCE, Federal Communications Commission (FCC), RoHS
Compliance certificatesCE, Federal Communications Commission (FCC), RoHS
Cooling
Cooling typeActive
Built-in fanYes
Weight & dimensions
Weight48.5 lbs (22 kg)
Width17.3" (440 mm)
Package weight52.9 lbs (24 kg)
Height1.73" (44 mm)
Depth28" (710 mm)
Packaging data
Rack mount kitYes
ManualYes
Cables includedInput power cable, Output power cable, RS-232, USB cable
Package weight52.9 lbs (24 kg)
Packaging content
Rack mount kitYes
ManualYes
Cables includedInput power cable, Output power cable, RS-232, USB cable